English Chinese Simplified Chinese Traditional French German Portuguese Spanish Russian Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
Leave Your Message

Air Filter Grading System Explained: From G4 to U17 in One Complete Guide

Decoding specifications, comparing EN 779 / ISO 16890 standards, and matching the right grade to industrial applications.

Understanding the Air Filter Spectrum

If you have ever stared at an air filter specification sheet wondering whether your facility requires an F7 pocket filter, an H13 HEPA, or a U15 ULPA, you are not alone. The global air filter grading system spans four main tiers—Coarse (G1–G4), Medium (M5–F9), HEPA (H10–H14), and ULPA (U15–U17). Each is engineered to target specific particulate sizes under rigorous test conditions.

Choosing the wrong grade can lead to premature filter failure, excessive energy consumption, or catastrophic contamination in sensitive environments. This guide maps out every grade in detail, explains how standard migrations (like EN 779 to ISO 16890) affect your procurement, and demonstrates how to build a cascading filtration system that optimizes performance and cost.

Key Takeaway: Modern filtration relies on progressive stages. A high-efficiency HEPA filter should never face raw, unfiltered air; it requires a strategic cascade of Coarse and Medium pre-filters to achieve its rated lifespan.
17f8c6619d20b867993b8457969a5c9

The Four-Tier Filtration Framework

From basic dust capture to sub-micron cleanroom protection, air filters are categorized into four distinct performance tiers.

Coarse Filters Icon

Coarse (G1–G4 / ISO ePM10)

Designed to capture particles larger than 10 μm, such as pollen, hair, insects, and heavy outdoor dust. Primarily used as pre-filters in HVAC systems to protect coils and downstream filters.

Explore Primary Filters →

Medium Filters Icon

Medium (M5–F9 / ISO ePM2.5 & ePM1)

Targets atmospheric dust, bacteria carriers, and fine combustion aerosols (1 to 10 μm). The F7 grade is the standard workhorse for modern commercial buildings and LEED ventilation specifications.

Explore Medium Filters →

HEPA Filters Icon

HEPA (H10–H14 / ISO 29463)

High-Efficiency Particulate Air filters capturing at least 99.95% (H13) or 99.995% (H14) of particles at the Most Penetrating Particle Size (MPPS, typically 0.1 to 0.3 μm). Vital for pharma and biotech.

Explore HEPA Filters →

ULPA Filters Icon

ULPA (U15–U17)

Ultra-Low Penetration Air filters offering up to 99.999995% efficiency at 0.12 μm. Reserved for high-tech cleanrooms, semiconductor fabs, and advanced nanotechnology laboratories.

Explore ULPA Filters →

The EN 779 to ISO 16890 Standard Transition

For decades, the European standard EN 779 classified air filters using simple letters and numbers (G1-G4, M5-M6, F7-F9). However, this testing method measured average efficiency against a single synthetic test dust size, which did not accurately reflect real-world ambient pollution.

Introduced globally, the ISO 16890 standard evaluates filter efficiency based on three distinct particulate matter size fractions: ePM1 (0.3–1.0 μm), ePM2.5 (0.3–2.5 μm), and ePM10 (0.3–10 μm). This provides engineers and procurement managers with a much more accurate prediction of how a filter will perform inside an actual air handling unit (AHU).

When buying replacement filters, it is crucial to understand that an old "F7" class is not a single fixed equivalent. Depending on the media design, an F7 filter could map anywhere from ePM1 50% to ePM1 65%. Always request dual-certified test reports to verify you are getting equivalent performance.

Why the Standard Changed:

  • Real-world Aerosol Simulation: ISO 16890 tests filters against actual outdoor particle distributions, not just a single laboratory dust.
  • Electrostatic Discharge Testing: Filters are tested with and without electrostatic charge, ensuring performance doesn't plummet after a few months of service.
  • Global Harmonization: Bridges the gap between the European EN standards and the North American ASHRAE 52.2 (MERV) systems.

Master Air Filter Efficiency Comparison

Use this comprehensive comparison table to cross-reference grades, efficiency ranges, and typical application environments.

Tier Category EN 779 / EN 1822 Grade ISO 16890 Equivalent Efficiency @ MPPS / Particle Size Typical Application Fields
Coarse G1 - G2 ISO Coarse < 50% Arrestance-based evaluation Simple ventilation, insect screens, coarse pre-filters
Coarse G3 - G4 ISO Coarse > 50% / ePM10 50% Arrestance > 90% (Coarse dust) AHU first stage, paint booth pre-filters, residential HVAC
Medium M5 - M6 ePM10 60% - 70% ePM10 efficiency ≥ 50% Secondary stage HVAC, food prep areas, paint booths
Medium F7 - F8 ePM1 50% - 70% / ePM2.5 70% ePM1 efficiency ≥ 50% - 70% Commercial office IAQ, pre-filtration for HEPA systems
Medium F9 ePM1 80% - 85% ePM1 efficiency ≥ 80% Data centers, hospitals, gas turbine intake systems
HEPA H10 - H12 EPA Range (ISO 29463) 85% to 99.5% @ 0.3 μm General cleanrooms, food processing, vacuum cleaners
HEPA H13 HEPA Class (ISO 29463) ≥ 99.95% @ MPPS (0.1 - 0.3 μm) GMP Grade B/C cleanrooms, biosafety cabinets, hospitals
HEPA H14 HEPA Class (ISO 29463) ≥ 99.995% @ MPPS (0.1 - 0.3 μm) GMP Grade A aseptic zones, semiconductor fabs (ISO Class 5)
ULPA U15 - U16 ULPA Class (ISO 29463) ≥ 99.9995% to 99.99995% @ 0.12 μm Semiconductor photolithography, wafer processing, nanotech
ULPA U17 ULPA Class (ISO 29463) ≥ 99.999995% @ 0.12 μm MPPS Ultra-clean environments, nuclear exhaust containment

Application Matrix: Matching Grades to Industries

Every industry has specific particulate standards. Below is how you should match filter grades to meet operational compliance.

Pharmaceutical Cleanrooms

Strict adherence to EU GMP Annex 1 is mandatory. Requires H14 HEPA filters for Grade A aseptic filling zones, and H13 filters for Grade B/C background areas.

Recommended: F8 + H14 Cascade

Semiconductor Fabs

Sub-micron particles destroy silicon wafers. Lithography bays and mask shops require U15 to U17 ULPA filters combined with chemical molecular filtration.

Recommended: F9 + H14 + U15

HVAC & Commercial Buildings

To achieve LEED credits and ensure occupant health, systems should combine a coarse pre-filter with a high-performance medium pocket or V-bank filter.

Recommended: G4 + F7 (ePM1 60%)

Data Center Cooling

ASHRAE TC 9.9 guidelines require protection against fine dust and corrosive salts. Multi-stage filtration prevents hardware failure and optimized PUE.

Recommended: G4 + M6 or F7
2a67e41574b403411a53b04d4a15296e

The Cascading Principle: Protecting Your Investment

Installing a standalone high-efficiency filter (like an H14 HEPA) in an air stream without proper pre-filtration is a critical engineering mistake. The high concentration of larger ambient dust particles will clog the micro-glass or ePTFE membrane of the HEPA filter within weeks, causing pressure drop to spike and airflow to drop.

The Cascading Filtration Strategy distributes the particulate load across multiple stages. Each stage is designed to capture a specific range of particle sizes:

  • Stage 1 (Coarse G4): Captures 90% of large dust particles, protecting the fan and cooling coils.
  • Stage 2 (Medium F7/F9): Removes fine sub-micron dust and soot, extending the life of the final HEPA filter by 3 to 5 times.
  • Stage 3 (HEPA H13/H14): The final barrier, capturing 99.95%+ of viruses, bacteria, and sub-micron particulates.

By allocating 15% of your filter budget to high-quality pre-filters, you can save up to 60% on overall replacement and energy costs over the system's lifetime.

Common Procurement Pitfalls to Avoid

When specifying and purchasing air filters, look out for these four common errors that can compromise performance.

1. H13 vs H14 Confusion

A 0.045% efficiency difference might seem minor, but it represents a tenfold increase in particle penetration. For GMP Grade A aseptic cleanrooms, using an H13 instead of an H14 will cause regulatory compliance failure.

2. Ignoring MERV-A Suffix

Standard synthetic filters can rely on electrostatic charges to achieve high initial efficiency. Over time, this charge decays in the field. Always specify filters with the "MERV-A" suffix to ensure stable mechanical efficiency.

3. Incorrect Test Aerosols

HEPA filters can be tested using different aerosol agents like DEHS, PAO, or DOP. Ensure the testing agent used by your filter manufacturer matches the downstream particle counters and validation protocols of your facility.

4. Buying "F7 Equivalents"

Under the ISO 16890 transition, some suppliers sell low-performance filters under old "F7-equivalent" labels. Always demand the exact ePM1 or ePM2.5 rating percentage to ensure you are receiving the correct filtration capacity.

Why Partner with KWS Purification?

Founded in 2011 in the beautiful coastal city of Xiamen, Xiamen KWS Purification Technology Co., Ltd. is a high-tech enterprise integrating R&D, manufacturing, sales, and technical service. Over the past 14 years, we have built a reputation for delivering reliable, certified air filtration solutions globally.

We operate advanced filter production lines, automatic mixing/filling machines, and state-of-the-art testing equipment. All KWS products undergo strict validation by third-party national authoritative organizations to ensure absolute compliance with global standards.

3baeffd37e59a5f9084815a40eca46c0
图片132

Our Core Competencies

We focus on high-performance materials and customer-centric customization to solve complex cleanroom and HVAC challenges.

01

Product R&D & Patents

KWS holds 15 patent certificates for air filter products (obtained from 2023 to 2025) and utilizes advanced ePTFE membrane technology for low pressure drop applications.

02

Customized Engineering

We provide non-standard custom sizes, specialized framing, and custom efficiency options to match unique air handling unit designs.

03

Fast Turnaround & Delivery

With optimized supply chains and dedicated production lines, we support short delivery cycles, with fast-track orders completed in 3-7 working days.

Our Scale & Commitment

At KWS, we believe that high-performance air filtration is built on a foundation of technical expertise and humanistic values.

14+

Years of Environmental Industry Experience

15

Air Filtration Product Patents

95%+

Employee & Customer Satisfaction Rate

3-7

Working Days Fast Delivery Cycle

The Humanistic Temperature

We firmly believe that a great company is driven by passion and employee well-being. By fostering a supportive workplace—offering flexible hours, health initiatives, and professional growth opportunities—we have been recognized as a "Best Employer" for three consecutive years. This internal care translates directly into how we serve our clients: with empathy, responsiveness, and a deep commitment to technical excellence.

Ready to Optimize Your Air Filtration System?

Whether you need standard G4 pre-filters, custom-sized F7 pocket filters, or ultra-pure H14 HEPA and U15 ULPA modules, KWS is here to assist. Let our engineering team help you design the perfect cascading system for your facility.

Request a Consultation View Full Product Line